Features | |
![]() |
Design Pressure: 6 bar | |
![]() |
Heat Output: 4000-6000 kW | |
![]() |
Efficiency: >92,0% | |
Available Certificates | Recommended Technologies |
![]() |
![]() |
![]() |
![]() |
![]() |
Main Applications | ||
Commercial facilities | Residential buildings | Hospitals |
Industrial heating systems | District heating | Sports centers |
Swimming pools and water parks |
Description |
Reverse flame fire tube heat boilers. Cylindrical furnace completely closed on the rear side by a convex bottom supported by a fully submerged stub. It can be used with forced draft burners for the operation on liquid or gaseous fuels. Designed for the use in systems with water temperature between 60 and 100°C. |
Advantages | ||
Advanced management technology | Maximum operating flexibility | |
The boiler can be equiped with programmable logic technology that allows complete compatibility with any data acquisition system, also allowing the adjustment of parameters through the display. | Thanks to the very high water content and the very high thermal inertia, the boiler is suitable for any system solution, even in the most difficult operating conditions. | |
Efficiency at all costs | Maximum security | |
Integrated solutions for increased performance and efficiency through flue gas heat recovery fully integrated into the structure of the boiler. | The generator has been designed in accordance with the strictest international safety regulations in force. | |
Easy, fast and safe installation | ||
The installation is very easy: you just need to connect the system to the electric, hydraulic, steam and discharge lines. |
Hot Water Boiler Options | ||||||||
Model | Heat output at 70°C | Flow thermal | 100% efficiency at 70°C | 30% efficiency at 70°C | Flue gas pressure drop | Hydraulic pressure drop | H2O volume | Empty weight |
REX | kW | kW | % | % | mbar | mbar | lt | kg |
400 | 4000 | 4333 | 92,31 | 91,80 | 9,0 | 98 | 4450 | 7420 |
450 | 4500 | 4865 | 92,50 | 91,90 | 10,0 | 124 | 4900 | 7920 |
500 | 5000 | 5402 | 92,56 | 91,90 | 10,0 | 63 | 6200 | 9530 |
600 | 6000 | 6480 | 92,59 | 91,90 | 12,0 | 91 | 6900 | 11330 |
Dimensions |
Model | H | L | L2 | P | P2 | ØC | N1 | N2 |
REX | mm | mm | mm | mm | mm | mm | DN/in | DN/in |
400 | 2326 | 1980 | 1780 | 4310 | 3596 | 600 | 200 | 200 |
450 | 2326 | 1980 | 1780 | 4660 | 3946 | 600 | 200 | 200 |
500 | 2529 | 2180 | 1980 | 4729 | 3948 | 650 | 250 | 250 |
600 | 2529 | 2180 | 1980 | 5261 | 4488 | 650 | 250 | 250 |
Standard Equipment |
Instruments for pressure control, including: |
Large dial 3 way test valve manometer |
Instruments for temperature control, including: |
Thermometer with large dial, scale 0-120°C High temperature safety thermostat with manual reset (110°C) PT100 thermocouple |
Boiler control panel IP55 1/N ~ 230V 50 Hz: |
The safety thermostat with manual reset (110°C) is INAIL approved |
The boilers destined to foreign countries will be provided with: |
High-pressure safety switch with manual reset |